Multimeter/Network Analyzer

PMM50 digital multifunction power analyser

PMM50 digital multifunction power analyser
Description
● For single-phase, two-phase, three-phase system
● Measurements: VL-L, VL-N, I, In, Pf, Hz, W, Va, Var, Kwh,  
     Kvarh, THD-U, THD-I, 1-31th harmonic;  
● 3 voltage and 3 current input
● Calculate the neutral current
● L1, L2, L3 power factors
● Four-quadrant energy measurement
● System running hours
● Demand for I, P
● Voltage input: 0-690 Vac, Current input: 0.05-5.5A
● Current transformer: 1. 10000/1.. 5
● Voltage transformer : 0.1-999.9
● Maximum demand time : 1-90min.
● 2 pulse output/digital input (according to order)
● RS485 communication interface: Modbus RTU 4800-57600bps

 
Characteristics
PMM50
Auxiliary supply
Operating voltage (Un)
85···265 VAC/DC
Power consumption
4VA
Frequency
45···65Hz
Voltage measurement input
Measurement range
10···690VAC L-L
Measuring mode
True RMS
Measuring input impedance
4MΩ
Method of connection
single-phase,two-phase,three-phase
Current measurement input
Reference current
1A or 5A
Measuring range
0,05···5.5A
Measuring mode
True RMS
Overload capacity
10A (Through the external current transformer)
Self-consumption
0,2VA
Accuracy
 
 
Measures
Voltage
± 0,2% according to IEC61557-12
Current
± 0,2% according to IEC61557-12
Power
± 0,5%
Power factor
± 0,5%
Harmonics
± 1%
Frequency
± 0,02%
Active Energy ±
CL 0.5S according to IEC62053-22
Reactive Energy ±
CL 0.5S according to IEC62053-22
Insulation
Insulation voltage
3kV for 1min,50Hz
Display
Display type                                                         14.2mm LED red digital tube
Ambient condition
Opterating temperature
-10···+55°C
Storage temperature
-25···+75°C
Housing
 
 
Flush mount 96*96mm
 
Size                                                
The panel cut-size 92*92mm
 
Degree of protection
 
IP40(optional IP54) on front
 
IP20 housing and terminals
Weight
400g
Standard
  
Reference standard
EN61010.1; EN60529; EN62053-21; EN62053-23;
N61000-4-2; EN61000-4-3; EN61000-4-4; EN61000-4-5; EN61000-4-6;EN61000-4-8; EN61000-4-11;EN61000-3-2
►Measuring: VL-L, VL-N, I, In, Cos, Pf, Hz, W, ΣW, Va, ΣVa,Var, ΣVar, Kwh, Kvarh, THD-U, THD-I, 1-31th harmonics
►System running hours
►RS485 communication (MODBUS RTU)